41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for canyon lake, ca


Map of Canyon Lake CA
Jimmy P.

Jimmy P.


Job Checkin

Arrived on site to perform heatpump diagnostic on 2006 Neil system. Upon arrival Mike stated that he’s lived in the house for approximately five years and Has had no issues or maintenance done. He states now for a couple weeks that the system has been short cycling and not getting to temperature and the only way for him to get it to turn on is by shutting it on and off at the breaker but even after that it’s only runs for a short period of time also creating a extremely high electric bill due to this. Began troubleshooting at air handler and found that everything was operational at this area, proceeded to outdoor unit and did full inspection and found that system was low on R22 refrigerant which was completely phased out January 1, 2020. system was also over amping and exceeding 21 Amp for what it’s rated for using a total of 23 Amps and higher till it shuts off. Also checked other electrical components and found at that the high voltage distributor has burning and pitting marks