Client stated no heating -Inducer would constantly run and the pressure switch would never close -The pressure switch had 24v and i was able to manually close the switch so that wasn’t the issue -Inducer draft motor port where hose hooks onto was completely clogged with soot -I cleared it with thermostat wire and now it has proper flow to the switch -Heating elements are working properly and the furnace is currently heating -A maintenance membership was highly recommended as the issue was due to improper maintenance