Performed AC diagnostic on 20-year-old Rheem condensing unit. Upon my diagnostic I found that the 30 amp fuse was blown and that the hermetic side secondary motor control was weak. 1. Found that 30 amp fuse is blown due to high amperage pull of compressor. 2. Secondary motor control hermetic side weak although still power and compressor but not supplying proper voltage. 3. High voltage relay has burn and pitting marks on contact points will lead to failure of system start up 4. Compressor saver kit is weak and no longer in range. Standard Specifications rated 189-277 MFD ACTUAL 185 MFD 5. Compressor pulling incredibly high amps due to age and wear and tear. 6. Ductwork in the attic is hard pipe and not insulated in certain areas 7. Suction line not insulated on evaporator coil causing condensation and water to drip. 8. System contains R 22 refrigerant which was completely phased out January 1, 2020 9. Previous company had charged Up system with refrigerant which indicates to me that t