Arrived on site to perform spring tune up on a 2002 rheem system. Condenser located in back yard. Furnace and evaporator coil located in attic. Client stated no issues. Had client cycled cooling mode on. Advised. Would be checked and inspected indoor and out door units. As well checked system operation and components and electrical connections. Replace filter and wash out door unit. Advised the summary of findings are as followed. Furnace 1. 2003 rheem system. 2. Filter was heavily hammered and Clogged and long over due which is allowing dirt to enter system. 3. 5 ton unit with only one return vent which is causing a a air flow restrictions on the amount of air going into system which Cause says to ice up as it not reducing all the air flow out. 4. Static pressure is really high about double what system static pressure should be at as this is caused by not enough return air going in. Should have at least another return on home. 5.Due to lack of filter change out slight dust is accu