Performed furnace maintenance on 1991 Rheem system. Paul my maintenance there were a few points concerns that need to be addressed. 1991 Rheem- 1. Found that igniter has high ohms and Discoloration from age and wear and tear this Component is responsible for lighting the burners. 2. System was completely covered and Contaminated in bird droppings and rat droppings. 3. Inducer motor was beginning to over amp due to windings becoming older 4. Measured static pressure(airflow) Within System this measured out to a total of 1.40 which is extremely high and restrictive this can cause problems with the heat exchanger overheating. Design static pressure is set up at .50 5. System had a 55° temperature raise, System is designed for a 50 this is indicating that heat exchanger is getting hotter than usual due to low Airflow 6. Indoor blower Compartment Where air is mixed and distributed is completely covered in dust and debris this can be a trigger for allergies and asthma 7. System was missing