41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for escondido, ca


Map of Escondido CA
Jorge C.

Jorge C.


Job Checkin

Arrived on site to perform FAU diagnostic on 21 year old Rheem unit. Homeowner states that his system is not heating the downstairs very effectively, but The upstairs gets extremely hot. System is original to the home, has owned the home for about 6 years now and has always had this issue. Has had someone come out in the past and thinks he did some kind of repair to the ducting but is not quite sure what exactly he did. I cycled system for heat. Verified proper heating sequence of operations. System came on and started heating normally. Ductwork is in very poor condition. There is a lot of rips and tears that have been patched up and different pieces that have been put together. Temperature rise is fairly high. Static pressure is also high due to poor ducting. Because of brand of unit and condition of it, explained to homeowner the possibility of the heat exchanger being compromised and the concerns that can bring. Offered to pull out heat exchanger and thoroughly inspect heat exchange