Performed furnace tuneup on 1979 Payne heater. Upon my maintenance customer Did not want heat exchanger inspected and did inform him that that it is part of the safety check but we did skip this part. Also found a few points of concerns For the system. Furnace- 1. Found an indoor blower motor is heavily covered in dust and debris 2. Ducting is not sealed and has air leakage all over. 3. Transformers in very bad condition due to overheating 4. Scroll wheel is a bit loose on shaft motor. Also heavily covered in dust which may have also throw in the wheel off the balance 5. Static pressure was .94wc Due to the ducts and return vents being too small resulting in air restrictions 6. Spark ignition is weak and struggles to light pilot when calling for heat Went over full condition and potential high risk points of where the system will fail And homeowner Mr. Nally Will not do any repairs due to it being operational. Recommended that heat exchanger is also inspected to To verify that it is