Performed AC/furnace maintenance on 2001 Rheem 3 system. Upon my maintenance there were multiple points and concerns that were addressed with the homeowners. Central furnace- 1. Found that heat exchanger was cracked on multiple tubes. This was caused due to overheating and the metal expanding and contracting Due to high temperature rise and Restricted airflow 2. Static pressure on system was 1.29 due to clog filters never been swapped out along with dirty evaporator coil. This is a major air restrictions due to the dirt buildup and has resulted in overheating conditions 3. Single secondary motor controls has become out of range Due to Motor using more power than needing from oil leakage 4. Indoor blower motor Lubricant seal has popped from high usage and AC mode most likely. If left in this condition can cause motor to overheat or lock up due to lack of lubrication. 5. Flame sensor has oxidized and can cause failure on ignition if left like this 6. Evaporator coil covered in dust and d