41638 Eastman Dr. Suite B
Murrieta, CA 92562
(888) 659-2665

Job Locations
for hemet, ca


Map of Hemet CA
Jimmy P.

Jimmy P.


Job Checkin

Performed AC diagnostic on 2003 Lennox Condenser. Upon my diagnostic client stated that system has recently stopped working and is no longer blowing out cold air. Although even when system was operational it still wasn’t keeping up and cooling down the home. I found multiple points of concerns that were addressed with Rosie. 3 ton condenser- 1. Outdoor condenser fan motor has become defective and is no longer cooling down the compressor or rejecting heat from the coils. This is why the system is screaming when the high pressure is relieved at the compressor relief valve. 2. Duel secondary motor control has become weak from over amping compressor and fan 3. Starter showing signs of painting and burn marks on contact points 4. System Contained R22 refrigerant which was completely phased out January 1, 2020 5. Power disconnect was not equipped with surge protection Discussed full condition of system with Rosie And she’s aware of what is going on with it at the moment. Informed her t