Job Checkin

Arrived on site to perform spring tune up on a 2014 lennox unit. Client stated no issues just wanted to check pressure. Condenser located in back yard furnace and Evaporator coil located in attic. Washed condenser coil inside and out. Primary starter is okay a bit worn out secondary motor control is good and in range. Fan motor is good checked compressor start up amps and was over amping on start up as it pulled 124 and max rated at 108. Advised not good and recommended adding a compressor booster kit to to prevent hard start ups. Run amps are good and in range. He led pressure and are good and cooling home at 20 degrees. Replaced filter and drain lines were clear at this time. Client supplied his own filter. No protection on either u it and recommended adding surge protectors on unit due to communicating , variable speed and zoned systems. Clips aware and did declined recommended work at this. Client also stated he would call in office to renew Plan. Client is aware how system runnin