Performed Furnace diagnostic on 17-year-old Goodman system. Upon my diagnostic there were a few points or concerns. 1. Found the circuitboard within furnace was experiencing intermittent behavior and was producing a chattering noise within the relays. Ultimately caused the inducer and the indoor fan motor to shut on and off. 2. Indoor blower motor was showing oil leakage from bearing. This can cause the fan motor to lock up and over amp 3. Motor control for capacitor was replaced once as well 4. Airflow was rating .80 exceeding the .10 designed for it on data plate. This could indicate airflow restrictions interfere with heat exchanger Recommendations- 1. Replace circuitboard with aftermarket board to prevent intermittent behavior 2. Replace condensing fan motor to prevent motor lock up