Job Checkin

Client stated no heating -Control board is receiving 24v -Inducer motor is working properly, but the pressure switch is not receiving any 24v from the board itself -I have power between C and W terminals -Control board needs to be replaced as it is not sending any voltage to the pressure switch -Client is becoming apart of our comfort club -Will return monday to install board