Arrived on site to perform furnace on 2004 heater. Upon arrival homeowner had to leave at start but explained unit Was not heating home off and thermostat had gone blank. He has recently change the filter and said in the summertime the AC was freezing on suction line in the middle of the night. Began diagnostic at indoor furnace and found that unit was operational. Measured temperature rising it was in range at 50°. Airflow was heavily restricted on the unit and clients and filter was very dirty prior to win thermostat went blank. Inspected indoor blower motor and found significant oil leakage running off of it which can result in overheating conditions as well. All supply vents are open. Platform underneath evaporator coil had significant water damage and on top of the unit recommend a secondary float switch to prevent flooding on ceiling. Discussed full diagnostic and condition with Samuel and he is aware that unit is original to home. At this time unit did not fail during my inspec