Arrived on site to perform spring tune up on a 2009 Goodman unit. Client stated no issues as they have yet to use system. Condenser located in back yard. Furnace and Evaporator coil located in attic. Washed condenser coil inside and out. Primary is burnt up on contact points from self wear. Secondary motor controls is good. Fan motor is working at max rate. Could fail in future from self wear. Checked compressor amps. Start ups was really high and over max from self wear and age. Run amps are good and in range. System pressure are good and cooling home at 20 degrees. System uses R-22 refrigerant and no longer in production. Inspected indoor unit. Filter was slightly dusty but good. Blower assembly and motor are good. Evaporator coil has slight dust and debris from past dirty that has entered system. No protection on out door unit. Cycled system. Went over all findings and recommendations with client. Client is aware of how system is and it’s condition. Client did declined recommended