Arrived on site to diagnose no cooling 2017 carrier unit client stated unit is working just not cooling and blowing warm air. Upon arrival client cycled unit and found compressor not on. Inspected electrical compartment and found secon Was completely bad for compressor. Needed replacement. Replaced to replace napery unit. Primary stater is good. Fan motor has oil to be leaking. Amp draws is pulling 1.8 and max rated at 1.4 advised is over amping but would like to get system maintenance and cleaned out before dying motor should be replaced just advised in case dose fail from over amping. Compressor start up are I. Range but recommended a compressor booster kit to help prolong life of compressor. Run amps are pulling 11 and max rated at 15. Advised working hard cause unit is dirty. Checked pressure and are stable and good and unit is cooling home. Found to what looked like oil under condenser and in the condenser coil showed client and advised pressure are okay now and to not let dog