Performed AC maintenance on two systems 2004 condensing units. Upon my diagnostic there were a few points of concerns that were addressed. 3 ton Lennox Downstairs (NON OPERATIONAL)- 1. Found that dual run motor control was completely puffed up and blown on both hermetic and fan side. Compressor was pulling too much power. 2. Condenser fan motor leaking oil from bearing resulting in higher amperage Pull 3. Compressor failing on lock rotor start up 4. Compressor pulling incredibly high amps at 14. This is been due to wear and tear in age of system. 5. Condenser coil appears to have coil rot occurring this is a huge red flag for refrigerant leaks 6. System contains R22 Freon which was completely phased out January 1, 2020. 7. Pressures appear to be slightly low 3.5 ton Lennox upstairs (OPERATIONAL)- 1. Condenser fan motor leaking oil from bearing and causing higher amperage pull in friction 2. Dual motor control becoming weak on fan side due to high amperage Consumption. 3. High voltag