Performed furnace maintenance on 2006 carrier system. Upon my maintenance guy came across a few points to concerns that were addressed with Ms. Judy. 1. Found that airflow was very restricted creating a 0.90 static pressure. This can cause complications for the heat exchanger when getting too hot. 2. found that flame sensor was a very bad condition and discolored, Component is responsible for sensing flame 3. Hot surface igniter it’s beginning to burn out and develop multiple hotspots 4. Recommended pulling heat exchanger due to high static pressure although customer would like to hold off for the moment and schedule a different day for that.