Jimmy P.

Jimmy P.


Job Checkin

Performed AC maintenance on two systems 2004 Carrier condenser’s. Upon my maintenance there were multiple points of concerns that were addressed with the homeowner. Downstairs condenser- 1. Found the condenser fan motor had significant oil leakage occurring from Bearing and Can Potentially lock up or over heat. Motor already showed signs of failure on start up due to the delay of the motors initial start up. 2.Starter showed signs of burn marks and pitting on contact points this component acts as the brakes for the system. 3. Duel secondary motor control has become weak on fan side terminals. This is initially caused due to the motor using more power than needed 4. System contains R22 refrigerant which was completely phased out January 1, 2020 5. Compressor was also locking out during the stress test which indicates to me that the compressor could potentially be dying. Compressor saver kit Reduce this problem from happening. Upstairs condenser- 1. Condenser fan motor is also leakin