Perform furnace maintenance On 2001 Lennox Heater. Did a safety inspection and electrical maintenance on heater. During the maintenance as I came across a few points of concerns that were addressed with the new homeowners. Furnace- 1. Found that thermostat was firing up in heating mode incorrectly by turning on the indoor blower first due to it being swapped into electric heat pump mode rather than gas mode. This is caused by the gas mode relay not working properly 2. Found single secondary motor control it’s rating at 41.78 µF +-5%. This is coming incredibly close to 42 and will be considered a weak motor control and will not be able to fire up or potentially cause the motor to over amp and overheat 3. Gas line did not have drip leg to increase life of gas valve. Not up to code. 4. Indoor blower cabinet was covered in dust and debris 2 to 1 inch filter not being swapped out consistently enough 5. Evaporator coil did not have secondary flow switch to prevent flooding that may occur