Job Checkin

Performed AC diagnostic on 2007 Ducane Condenser. Upon my diagnostic Mario stated that just a couple months ago The heater had issues with the circuitboard and it needed to be replaced and now the AC doesn’t turn on. The first place I went was to the thermostat and turned the system on to cooling and there was a tremendously long delay. Removed thermostat and jumped out cooling and everything fired up. Proceeded to the addict define that the system is a dedicated horizontal Ducane Inspected the circuitboard and found multiple burns and heat spots. Also found that the indoor blower motor was leaking significant oil from the bearing. Inspected outdoor unit and measured refrigerant pressures to find that the system has major air Restrictions. Refrigerant charge checked out although it does have a Phased out refrigerant called R22. Measured duel secondary motor control that powers compressor and fan and found that it was weak on the compressor side. High-voltage relay was also pitted on