Job Checkin

Performed AC diagnostic on 1999 Goodman condenser. Upon my diagnostic client stated that the system stopped working about a week ago he’s not sure if the capacitors bad. Upon my diagnostic I found multiple points of concerns that were addressed with Woody. 1. Compressor windings are no longer good and are instantly causing the breaker to trip or pop the fuses. 2. Duel secondary motor control has been blown on both fan and hermetic side terminals 3. Power disconnect was no longer sending out load to condenser. 4. Starter showed signs of painting and burn marks on contact points 5. System Contained a Phased out R22 Refrigerant As of January 1, 2020 Discuss the full condition of the system with Woody and he plans on putting the house on the martlet. We are going to give him his options whether or not he would like to replace the R22 compressor or replace the ac side of the system. Upon departure collected only diagnostic fee and supervisor will be getting back to him about replacement o