Performed furnace maintenance on 2001, 2 system Bryant heater. Upon the maintenance this is turned into a diagnostic duty heaters both being non-operational and tripping on high limit. 1. Found temperature rise was 83° which is incredibly high from what it is specified on the data plate 2. Both high limit switches are going bad due to it consistently in the years before being tripped. 3. Heat exchanger from downstairs was verified cracked. Discovered the crack on a dimple due to high temperature rise and low Airflow. 4. Downstairs blower scroll wheel was off-balance creating a screeching noise readjusted and noise is gone Recommendations- 1. Replace heat exchanger if available 2. Increase airflow by cutting in new return intake 3. Replace both high limits to prevent heating problems 4. System replacement options