Service call that the AC was not working. Upon arrival found Thermostat was blank and the system was not running. The Condensation Pump had filled and failed to pump out, shutting the system down in Safety Interlock. Removed the Condensation Pump to inspect. Blew through the Vinyl Tubing to ensure it was clear. Found debris stuck in the Discharge Check Valve of the Pump. Removed the Check Valve Fitting to Clean. Removed debris and reassembled Pump. Put system back in operation. Filled Condensation Pump 15 times to ensure that it was pumping out properly. There is no visible damage to the pump that was found. The debris that was clogging the Check Valve may come from the Pump Motor. Spoke with Homeowner about issue and replacing the Pump. If something internal has broken apart and the pump clogs again, recommendation would be to replace the Condensation Pump. Included an estimate for the replacement of the Pump.