Performed QA on Trane Gas Furnace/AC System. Tested gas pressures and combustion. Found high stage gas pressure set to 1.6” WC. Adjusted both high and low pressures and retested combustion. Reviewed all programming on system. Tested the wet switch and ez trap safety. Found drain tubing inside furnace was not pitched correctly and was holding water. Cut tubing to increase pitch. Poured water through condensate trap to test. Completed checklist form in system. No additional follow up is needed.