Found Lennox gas furnace locked out on a code 3 pressure switch stuck open with inducer motor on. Checked venting for debris, checked pressure switch tubing for a clogg, no clogs were found. Excercised pressure switch and found inducer motor was very hot to the touch, got furnace to come on and heat came on. Recommend to replace inducer motor and pressure switch due to Lennox had issues with .65 pressure switches corroding internally. Will get price and availability tomorrow and get back to the customer with a quote.