Heat pump not working properly, found outdoor unit on code 3 short cycling on high or low pressure switch, reset unit and check heat pump operation check supply and return air, noticed after minutes of running unit goes off on high head, new filter, and good split, removed refrigerant from unit to bring down high around 300 psig data from specifications, ran unit for more than 30 mins, re check supply and rerun air ok, 94/63 F outdoor temp 40 F ......320/100 410A pressures system is running within manufacture specifications