Found all thermostats to 4 indoor heads to trane mini split system displaying e 3 error code. Checked over online Manuel and found that it was a low pressure cut out error code. System was charged up by another company before. Pulled disconect for a full 5 minutes then mini split came back on and has a suction pressure of 128 with all indoor units running. At this time nothing further needs done. Pressures are not low but they will need to keep an eye on the system and if problems whould re occur an extensive leak search will need to be performed.