Keeprite furnace maintenance, adjusted first stage gas pressures , fan speeds for blower motor were backwards on first stage and second stage , switched blue and red , vent drain diverter was plugged , removed blockage , inducer motor bearings starting to wear out and make noise on start up , humidistat was set to 10 % rh , adjusted to 40% also noticed old eac filter system , still works just inefficient