diagnosed condenser fan motor not starting on occasion. capacitor is a 3 microfarad testing at 3 microfarad. able to start motor by giving it a push start with a stick. advise customer that this means the motor is failing quoted motor and blade approximately $1,000 to repair. customer would like estimate to replace would like us to check availability on parts. scheduling estimate for replacement. also here to install automatic damper, supply house sent the wrong damper ordering correct damper.


diagnosed condenser fan motor not starting on occasion. capacitor is a 3 microfarad testing at 3 microfarad. able to start motor by giving it a push start with a stick. advise customer that this means the motor is failing quoted motor and blade approximately $1,000 to repair. customer would like estimate to replace would like us to check availability on parts.

scheduling estimate for replacement.

also here to install automatic damper, supply house sent the wrong damper ordering correct damper.