5349 Dupont Road
Parkersburg, WV 26101
304-863-3553

Job Locations
for reynoldsville, wv


Map of Reynoldsville WV
Corey B.

Corey B.


Job Checkin

Service Call Platinum Client furnace giving code 6 (vent intake or termination error) customer states that it was giving code 13(vent intake or termination error) system draws from inside. checked flue, no obstruction or belly. found water in the top of the inducer, inducer motor has water in it. found drain trap to be clogged. cleared drain trap system draining now. this has been a recurring issue, recommended installing a condensate pump and draining out into washing machine drain. quoted pricing, customer accepted but needs to get to work soon. scheduled for Friday to install condensate pump

Service Call Platinum Client

furnace giving code 6 (vent intake or termination error)

customer states that it was giving code 13(vent intake or termination error)

system draws from inside. checked flue, no obstruction or belly. found water in the top of the inducer, inducer motor has water in it. found drain trap to be clogged. cleared drain trap system draining now. 
this has been a recurring issue, recommended installing a condensate pump and draining out into washing machine drain. quoted pricing, customer accepted but needs to get to work soon. scheduled for Friday to install condensate pump