Performed Platinum Comfort Club Membership Tune-Up on Heating System inducer amps 1.56 blower amps approximately 5.45 blower cap tested within range did adjust gas pressures from 3.78 to 3.25 in accordance to york parameters temp rise 48 deflate sensor cleaned do also suggest adding surge protection to furnace as well Performed Platinum Comfort Club Membership Tune-Up on Cooling System pressures were 111/198 sat 37 @58 degrees ambient. capacitor tested under load read within range compressor amps 9.98 manufacturing RLA @23.7 fan amps @.67 coils clean do suggest adding surge protection to unit due to unit having ECM fan and board drivers very receptive to any type of surging or overcurrent. no issues at this time.
We will pull the power to the new location of the furnace and adapt to the ductwork