Arrived with gas valve prior technician had diagnosed. Install gas valve. Leak checked pipe. Adjusted gas pressure to 3.45 w.c. Temperature rise in range. Performed silver club furnace maintenance. Capacitor and motor amp draw in range. Induced draft motor in range. Cleaned flame sensor and tested ignitor. Cycled unit multiple times to insure that all safeties are working and unit running as designed. Replace batteries to thermostat. Found water on top of furnace flue was leaking due to some issues with prior service call I sealed flashing at no charge to customer. System is heating at this time. Customer had 25.00 gift card I applied towards balance.