05JUL2023 Jason Brown Arrived for summer tune up service. Spoke with homeowner about the systems performance. The garage system thermostat is out. The home system is working well. Inspected garage package unit found disconnect has a loose connection with the fuse. Washed both condenser coils. Cleaned out electrical cabinets, inspected disconnects, line voltage, condenser fans, abd blower motors. Verified coils were clean and checked charge. Found Carrier condenser is good condition fan at .9a compressor at 10a reversing valve switches properly and charge on point. Blower wheel and motor good. Found disconnect for garage package unit not making a good connection with fuse. Found blower capacitor reading 12/12.5 blower reading 3.5 and compressor at 14a all within manufacture specifications. Spoke with homeowner about my findings, we decided to go ahead and get the disconnect replaced. Will call with availability tomorrow. Both systems are clean and operating properly at this time