Jake Kring. 05-09-2023. I arrived for a blue club member no cool call. I inspected the system and found one 30 amp fuse to have blown. I replaced the fuse and found the condenser fan motor to be over amping and making a grinding noise. The motor shuts off and and is causing the compressor amps and the motor amps to rise blowing the fuse. I explained this to the homeowner and we decided to replace the warranty fan motor. The part should be sent to the shop 05-09/10-2023 and we will be out to replace the motor when we get the part delivered to the shop. Jake Kring. 05-10-2023. I arrived to replace a warranty condenser fan motor. I removed the old motor and installed the new motor and cycled the system and and checked all components and found the noise to have lessened and the amp draw to be within normal range. The warranty on the motor will last until the original warranty on the system.