Austin 2-7-25 Completed the service call visit on the carrier equipment after thoroughly investigating the equipment and trying to ascertain the issue at hand. I did discover that the filter and the system was way too thick and it was having a extremely hard time getting errors through the return because it was dirty and it was a Merv 12, which you should never use more than a Merv 10 but also after investigating the equipment, I adjusted the gas pressure as well so that it wasn’t going to burn as hot and the temperature won’t rise as much but then I went into the attic to check on the flu and the ductwork and I discovered a 6 inch duct, that had two wise on it, and one of the wise was capped off, and a big portion of the ductwork was collapsed and no longer connected properly, which is a big issue with the system as well since it cannot circulate The air properly it could cause a major issue on the system and was part of the issue at hand. Also, the roof was replaced in the summertim