Came out to call to check two package units over and see if they need to be repaired or replaced. Found both systems throwing breakers due to bad compressors. 6 ton unit has melted leads on the compressor and was immediately throwing the breaker. 5 ton unit would try to run, and then throw the breaker. Units are from 2004 and run on R22. I highly recommend customer look into replacement options rather than repair, due to age, condition of the rest of the system, and the refrigerant no longer being produced. I can’t guarantee how much longer R22 will be available.