Jake k. I arrived and found the system to be on a lock out. I contacted Goodman tech support and found that we need to tilt the furnace forward 1/2 to 1”. The system will run for about 15 minutes after I remove and drain the induced draft motor then it starts to shut the pressure switch off causing the system to shut down and repeat this process three times locking the system out. I spoke with two different techs on this issue and we all agreed to remove the furnace and reinstall the furnace at a tilt. Claim # 2192506 Goodman tech support. 10/31/2023 JeremiahF Arrived at clients residence and went over scope of todays service. Pulled blower motor out from compartment to make room inside blower compartment to work, lifted back of furnace and placed vibration dampers to get 1/2 of lift for for forward tilt of furnace. Resealed the unit and reinstalled the blower. Flame shutting off and immediately beginning ignition sequence after flame dies. Checked to make sure the diaphragms in bot