Jake K. I arrived for new system no cool call. I inspected the system and found the pressure switch on the furnace to be stuck closed and kept the system from cycling the furnace on. I then inspected the air conditioning and found that the blower motor will not come on in cooling. The thermostat was not calling for fan on in cooling. I replaced the thermostat and cleaned the pressure switch and found the system to be running in all modes correctly.