Austin 2-20-25 Came out for the service call visit to check on the Lennox air handler and during the visit I discovered that the sequencer was not sending proper voltage over to allow the heat strips to come on and work as intended. So after speaking with caitlyn, we got approval to get it swapped out and after doing so I discovered that. I could only get one heat strip working on the system because the other heat strips are bad which is probably why the sequencer went bad in the first place however, they have more heat now than when I arrived so we are certainly going in the right direction on getting them fixed up All the way but as of now it is not at its full heating capacity on the electrical heat strips, but after talking to Miss Kaitlyn, she is going to speak to the landlord to get some more information on some financials and call into the office to get it scheduled and taken care of which is totally understandable And we will patiently await her phone call, but as of now the