-Performed CMA Full Service on 7 Split System Heat Pumps. Verified operation of kitchen oven hood exhaust and make up air. -System 1: Blower capacitor inaccessible. Unable to remove blower wheel for access due to location of unit. Recommend replace capacitor due to age & relocate to accessible location. -System 2: Fire alarm shut down not connected. Heat strips contactor not wired. -System 3: Sure switch for primary drain line is in poor condition and will not operate in the case of a drainage clog. Recommend replacement of overflow safety switch. No float switch installed on auxiliary pan. This has been recommended prior. Found fan runs with thermostat off of wall. Suspect problems with blower motor relay/board. Maintenance is okay with constant circulation, but system may need diagnosis on fan board if correction is needed. -All systems operating correctly at this time.