2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Local Reviews
for burgaw, nc


Job Locations
for burgaw, nc

Jesse J.

Jesse J. Job Checkin

Tech preformed CMA INSPECTION on 8 Split Systems. Split System #5 is operating at this time but both condenser coil and evaporator coil are in poor condition, system is 29 years old. Tech does recommend replacing system. All other systems are operating at this time. Tech has attached system performance reports to invoice along with pictures.


Donald  S.

Donald S. Job Checkin

Installed filter grill inside system and cleaned trash in the attic System 3 did not have a filter grill and will need one as well.


Matthew L.

Matthew L. Job Checkin

Tech replaced crushed start collar for return on Trane air handler. Secured new start collar with 3 screws and sealed with mastic tape. Reconnected 6” flex duct and secured with 2 panduits, mastic tape and FSK tape. There used to be a 12*20 filter inside old air handler. There is no filter slot in return box and no filter slot available inside new air handler. Returns in ceiling are fire dampers. AHU 2 needs a filter slot cut. Jerry says they take care of their own filters. Tech let staff on site know.


Luis R.

Luis R. Job Checkin

Tech found a 6in return flex on floor with collar all bent up tech was able to reattached to return box will need to return with new 6in start collar at earliest convenience unit is operating properly at this time


Matthew L.

Matthew L. Job Checkin

2023 model Trane AHU 3 indoor coil frozen. No filter installed. No filter slot in AHU. Returns are fire dampers that cannot accept filter. Need to cut filter slot for AHU3. Tech allowed system to thaw while diagnosing other unit. 2017 model Goodman AHU 6 dripping into aux pan and draining from aux drain line. Kenny got pic July 19. 2023 model Carrier AHU 3 no filter installed. Installed 20*25 filter inside AHU. Trane 2010 model AHU 4 appears no longer on site. Carrier AHU installed 12 days ago. Tech found thermostat blank due to black line voltage wire not seated into polarized plug. Transformer only getting 120v. Seated plug. Programmed Vision Pro from factory startup. Allowed system to cool for 10 minutes without issue. Recorded pressures. Tested drain. Tested heat mode and defrost cycle. Returned to system 3 after getting system 4 cooling and ensured indoor coil is thawed out. Tech found true suction service port valve core leaking below switchover valve. Uploaded picture. Tighte


Dalton  B.

Dalton B. Job Checkin

Unit #4: Dining Room


Luis R.

Luis R. Job Checkin

Upon arrival thermostat was satisfied tech did ensure blower motor was at high speed airflow was correct in vents maintenance man did mention dinning area unit is down and unit 3 is trying to cool that as well tech did educate if all units are not operating correctly then unit will not be able to keep up as needed


Kenny C.

Kenny C. Job Checkin

Upon arrival tech found drain line clogged up and kitchen hood vents were on, not allowing to cool off kitchen. Pressures were within spec. Tech flushed out drain line and informed maintenance personnel to turn off hood vents inside kitchen. System is back up and cooling.


Kyle W.

Kyle W. Job Checkin

UNIT #4 2022 MODEL CARRIER CONDENSER PAIRED WITH 2010 MODEL AMERICAN STANDARD AIR HANDLER. FOUND INDOOR TXV RESTRICTION. $1996.00 PLUS TAX FOR TXV. SPOKE WITH MR. CUPP. HANDED OVER TO COLBY FOR PROPOSAL ON AIR HANDLER.


Kyle W.

Kyle W. Job Checkin

SYSTEM #3 EVAPORATOR COIL IS LEAKING. SPOKE WITH MR. CUPP. TOPPED OFF WITH REFRIGERANT FOR TIME BEING. ALSO SPOKE REGARDING CAPACITOR THAT WAS RECENTLY REPLACED ON SYSTEM #3 THAT WILL BE WORKED INTO PROPOSAL. FORWARDED TO COLBY TO WORK ON PRICING FOR REPLACEMENT.


Dalton  B.

Dalton B. Job Checkin

Unit #2 (Right Hall)


Jesse J.

Jesse J. Job Checkin

Tech preformed recommended repairs from previous service. Breaker for AHU#1 was already replaced upon arrival. Tech checked unit and system is operating correctly at this time. Tech replaced capacitors on AHU#5 and HP Cond#3. Tech has attached pictures to invoice. Units are operating at this time. Director expressed concerns about Lobby / office unit. Tech advised director that leaking coil was diagnosed from previous visit and estimates were being calculated for repair vs. replace.


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA FULL SERVICE on 8 split systems. System 1 and 2 are both down at this time due to power challenges. System 3 is operating at this time but low on refrigerant due to leaking evaporator coil. All other systems are operating at this time. Tech has attached performance reports to invoice along with estimates for any minor repairs needed.


Randy K.

Randy K. Job Checkin

Full service on 3 Trane gas furnaces, AC systems, changed filters.