Unit 2 air handler had correct 30 amp breaker in main panel. Non fused disconnect at air handler. Unit 2 condenser needed 15 minimum or 25 amp maximum. Installed 20 amp breaker in main panel for unit 2 condenser.
PERFORMED CMA FULL SERVICE ON 8 SPLIT SYSTEMS. SPLIT SYSTEM #4 DUAL RUN CAPACITOR RATED 70/7.5mf TESTED WEAK ON COMPRESSOR SIDE AT 67.9mf. CAPACITOR DUE FOR FAILURE. RECOMMEND REPLACEMENT OF CAPACITOR. REPLACEMENT OF DUAL RUN CAPACITOR 70/7.5mf WOULD BE. ALL OTHER SYSTEMS ARE PERFORMING PROPERLY. PERFORMANCE REPORT AND PICTURES ARE ATTACHED TO THIS INVOICE.
(DOWNSTAIRS) 14 YEAR OLD SYSTEM. FOUND SYSTEM PRESSURES WITHIN SPECS. COMPRESSOR WINDINGS ARE BEGINNING TO FAIL. RATTLING DURING OPERATION, EXTREMELY NOISY ON STARTUP, LOW AMP DRAW, AND ALL (3) WINDINGS READING BAD AT OHM METER. EVAPORATOR COILS HEAVILY RUSTED. COSTLY REPAIRS NOT RECOMMENDED. (UPSTAIRS) 22 YEAR OLD R22 SYSTEM. HANDED OVER TO FIELD SUPERVISOR BOTH SYSTEMS.
PERFORMED PTU ON (1) TRANE SPLIT HEAT PUMP. INVESTED IN PSA (1) SYSTEM. VERIFIED SUPPLY BOOTS ARE PROPERLY IN TACT.