-Performed CMA Inspection on 6 split systems. Dual air handlers & evaporator coils on systems 3, 5, 6. Verified operation of oven hood exhaust and make up air. -Split System 1: System was recommended for replacement August 2023. R22 system ~25 yr old. System found frozen at condenser and line set at that time. Compressor failed megohmeter test and found to have shorted windings. --Split System 2: System was recommended for replacement August 2023. R22 system ~25 yr old. Compressor failed megohmeter test and found to have shorted windings. Found evaporator coil in poor condition and corroded. Temperature difference was found to be insufficient. System has relatively new furnace and was recommended to replace condensing unit and evaporator coil. Outdoor fan motor not operating via contactor. Observed extreme delay in operation and fan motor running at excessive amperage. Rated at 0.98 FLA on unit, 1.6 on motor; running at 3.26. 208/230 1/6 HP 1625 rpm. Provided estimate for motor repla