Performed CMA Inspection on 11 split systems and 1 mini split system. -Split system on 2nd floor that services 2nd floor offices fan capacitor rated 10mf tested weak at 7.31 mf. -Recommend replacement of capacitor, there is an estimate attached to this invoice for replacement of capacitor. - Split system #5 at truck was station had a low delta T and system is not cooling properly. -System is low on R401 refrigerant, tech did not have gauges present during services to tell how low on refrigerant system is. - Tech performed a leak search on system and didn’t find any leaks. - There could be a leak present in line setting, tech recommends a level 2 leak search for system to pin point possible leak.- There is an estimate provided for level 2 leak search and an estimate provided for 1 pound of refrigerant. - System may need more than 1 pound of refrigerant, refrigerant is priced by pound. - All other systems were performing and cooling properly with a delta T above 18 degrees. - Tech checke