Spencer C.

Spencer C.


Job Checkin

Tech found 24v at Y and T1 but no voltage at T2. Tech bypassed T2 and sent T1 straight 2 the contactor. System was running properly. This is not bypassing pressure switches as pressure switches power from Y and are ran in series with T1. T2 is only used for defrost and time delay. Tech quoted defrost board. Disconnect spades were also broken off the handle and stuck inside the disconnect. Tech quoted replacing disconnect. Tech also found condenser coils are corroded from the salt air.