{Upstairs Split System} - Found failed capacitor and compressor drawing high amps. Recommended a start kit to increase efficiency and extend life of the compressor. Customer approved. - Replaced capacitor with a turbo 200, installed a start kit, and confirmed proper operation with delta T measuring 15.5. - Advised customer that the condenser fan motor is drawing 1.24 amps with a FLA of 1.4 amps. Advised the motor is failing and may need to be replaced in the future. {Downstairs Split System} - Customer requested diagnosis on site. Tech found condenser not running with contactor pulled in. Found tripped breaker and began trouble shooting by isolating the compressor, observing no issues. Checked compressor and found windings measuring in the red zone on megohm reader. Confirmed not grounded. Compressor needs to be replaced. - Customer approved compressor replacement. Office will order compressor and contact customer with ETA and scheduling. Upstairs system is operating normally at th