Found the condenser with high head pressure of 428 and 94 on the suction. 20+ year old split straight AC system. New thermostat, thermostat wire, contactor, and capacitor were replaced by another company. Tech did record the condenser fan amp draw that’s at limit and high compressor amp draw as well. R22. Tech diagnosed a restriction within the system. The compressor was hot and the fan motor will turn off once it gets too hot as well. The condenser coil is hot to the touch. Indoor system is dirty as well. Costumer decided to receive a system replacement quote from us, this challenge has been happening for months now. Need to schedule a field supervisor to provide a solution. Collected house call fee only via cash.