-Observed heat strip contactor stuck when calling. Observed high discoloration on contactor winding. Observed arcing when engaging. Recommend replacement of contactor. 2 pole 40 A. Disconnected heat strips to maintain safe operation of air handler. -Replaced heat strip contactor per prior approval and verified operation of auxiliary heat.