Derek J.

Derek J. Job Checkin

Upon arrival tech was informed system was not cooling at all. Tech found condenser running but blower was reading error of controller. Reset controller and blower came back on. Continued checking over system and found circuit 1 low on R410A Freon. Performed leak search and found leak at evaporator coil. Samuel stated they were going to reach out to company that installed system due to not having manufacture warranty. They said they would call us back after doing so. Office will need to quote for new coil replacement if we do repair.


Percy M.

Percy M. Job Checkin

TECH PERFORMED CMA FULL SERVICE ON 2 SPLIT SYSTEMS. ALL SYSTEMS ARE PERFORMING PROPERLY AT THE CURRENT TIME. TECH COMPLETED FILTER CHANGE OF 2-14x20x1 FILTERS THERE ARE PICTURES AND A PERFORMANCE REPORT ATTACHED TO THIS INVOICE.


Percy M.

Percy M. Job Checkin

TECH PERFORMED CMA INSPECTION ON 1 SPLIT SYSTEM AND 1 GAS FURNACE. SPLIT SYSTEM HAS A PROPER DELTA T READING, SYSTEM IS COOLING PROPERLY. SPLIT SYSTEM FAN CAPACITOR #1 RATED FOR 10mf TESTED WEAK AT 8.89 mf. CAPACITOR DUE FOR FAILURE. RECOMMEND REPLACEMENT OF CAPACITOR. WITH A MEMBER SAVINGS OF $36.70 REPLACEMENT OF THE #1 CAPACITOR WOULD BE $222.00. SPLIT SYSTEM FAN CAPACITOR #2 RATED FOR 10mf TESTED WEAK AT 8.77mf. CAPACITOR DUE FOR FAILURE, RECOMMEND REPLACEMENT OF CAPACITOR. WITH A MEMBER SAVINGS OF $36.70 REPLACEMENT OF 10mf CAPACITOR #2 WOULD BE $222.00. TECH WAS GIVEN APPROVAL TO REPLACE CAPACITORS #1 AND #2 BY MR. SAM. TECH COMPLETED REPLACEMENT OF 2 10mf CAPACITORS FOR SPLIT SYSTEM CONDENSER UNIT. TECH COMPLETED FILTER CHANGE OF 4-16x25x2 FILTERS AND 1-20x25x2 FILTER. THERE ARE PICTURES AND A PERFORMANCE REPORT ATTACHED TO THIS INVOICE. SPLIT SYSTEM FAN CAPACITOR #2 RATED FOR 10mf TESTED WEAK AT 8.77mf. CAPACITOR DUE FOR FAILURE, RECOMMEND REPLACEMENT OF CAPACITOR. SPLIT SYS


Percy M.

Percy M. Job Checkin

PERFORMED CMA FULL SERVICE ON 2 GAS PACKAGE SYSTEMS, 1 SPLIT SYSTEM, 2 DEHUMIDIFIERS, 2 MAKE UP AIR SYSTEMS AND 6 EXHAUST FANS. ALL SYSTEMS ARE PERFORMING PROPERLY AT THIS TIME. COMPLETED FILTER CHANGE OF 7-20x20x1 FILTERS, 4-20x20x2 FILTERS AND 8-20x25x2 FILTERS. REPLACED 4 FILTER GRILLS, 2 IN KITCHEN AREA AND 2 IN STORAGE AREA. RECOMMEND REPLACEMENT OF 3 MORE FILTER GRILLS, 2 IN LOBBY AND 1 IN COOKING AREA. REPLACEMENT OF THOOSE 3 FILTER GRILLS WOULD BE $736.50. PERFORMANCE REPORT AND PICTURES ARE ATTACHED TO THIS INVOICE.


Spencer C.

Spencer C. Job Checkin

Tech found the hot surface igniter only partially lighting. Igniter would have to be replaced. Tech noted unit is 20 years old and will need to be replaced soon. Tech verified heat exchangers were not cracked. Tech replaced igniter and found system heating properly. Tech also made sure all vents are blowing heat.


David  S.

David S. Job Checkin

-Performed CMA Filter Change on 2 Gas Package Systems and 2 dehumidifiers. Replaced air filters at 7 locations in back of house. -Management states challenges with heat upon arrival in the morning. Performed check of kitchen gas packs per approval by Mrs. Hubbard. Found improper gas pressures on gas pack 848D. Adjusted gas pressure per approval by Mrs. Hubbard. System now heating correctly. Found no ignition on gas pack 388D. Found voltage to igniter and gas valve as appropriate. Gas pressure to inlet side of gas valve is correct but found no change to outlet pressure when valve is powered. Recommend replacement of gas valve. Provided estimate $811.56. Did not visibly confirm igniter working correctly. System may need further diagnosis once gas valve is approved. Demand tech to be dispatched to verify findings. - Observed lobby split system thermostat set to emergency heat. Performed hard reset of split system, set thermostat to heat setting, and observed system running correctly in


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA INSPECTION on 4 VRV Condensers, 13 Air Handlers, 1 Exhaust Fan and 1 Air Makeup unit. All units are operating within specifications at this time. Tech has attached system performance reports to invoice along with pictures. Tech was asked if he could look at wall mount head unit in room 23 and 25 because they were making noise and not heating correctly. Tech observed that blower wheel and motor were excessively noisy and not moving a lot of air. Tech believes blower motor and wheel are failing. Tech suggests replacing blower motor and wheel. Office will have to price out repair and check availability on parts being head unit is 12 years old if customer wishes to proceed.


Chris M.

Chris M. Job Checkin

-Performed CMA full service on one split system with rooftop condenser, gas furnace and air handler. -Outdoor fan motor capacitors tested weak. Recommend replacement of both capacitors. Provided estimate $406.83. -Found manual damper to switch from furnace to air handler. Switched to furnace as appropriate. Educated warehouse staff about location and operation of switch.


Chris M.

Chris M. Job Checkin

-Performed CMA full service on 2 split system. -Split system 1: Reusable filter in air handler inaccessible. Recommend addition of filter slot in return duct to install replaceable air filter, or installation of filter grilles at return ducts. -Split System 2: Nearby sewage clean out exposed creating unsanitary conditions near condenser. No insulation on primary drain line. Recommend insulating drain line to prevent condensation buildup in attic. Approximately 25’. Provided estimate $383.66. Recommend installation of EZ Trap to properly service condensate drain line. Provided estimate $138.80. -Both systems operating correctly at this time.


Percy M.

Percy M. Job Checkin

PERFORMED CMA INSPECTION ON 2 DEHUMIDIFIERS,1SPLIT SYSTEM,1 MAKE UP AIR, 4 EXHAUST FANS AND 2 GAS PACK UNITS. AL SYSTEMS PERFORMING PROPERLY.


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA FULL SERVICE on 4 VRV Condenser units, 13 Air handlers, 1 Air makeup unit and 1 exhaust fan. All units are operating at this time. Tech has attached system performance reports to invoice along with pictures.