Percy M.

Percy M. Job Checkin

PERFORMED CMA INSPECTION ON 6 SPLIT SYSTEMS AND 1 MINI SPLIT SYSTEM. DUAL RUN CAPACITOR RATED FOR 70/5mf TESTED AT 57.7 mf on THE 70mf side. CAPACITOR DUE FOR FAILURE. RECOMMEND REPLACEMENT OF CAPACITOR. WITH A MEMBERS SAVINGS OF $53.33. 70mf CAPACITOR REPLACEMENT WOULD BE $322.61 ALL OTHER SYSTEMS PERFORMING PROPERLY.


Matthew L.

Matthew L. Job Checkin

Tech replaced filters.


Matthew L.

Matthew L. Job Checkin

Outdoor condenser 7 was off at disconnect. Staff reported lineset on outdoor unit 7 freezing up. Not outdoor coil. Restored power and found high pressure switch tripped in heating mode very quickly. Switched to cooling mode and lineset started freezing up. Tech went in search of AHU 7 to confirm blower operation. Attic access in the middle section of back hallway is for AHU 7. Tech confirmed seized up 3/4 hp 1075 rpm blower motor. Tech recommends replacing 19 year old R22 split system over repairing due to cost of blower replacement, age, and EPA phase out of R22. Let Jeff Cupp know of findings. Need to provide repair vs replacement estimates. Let Gina know.


Luis R.

Luis R. Job Checkin

Tech was informed unit 14 thermostat was blank tech found thermostat did have power and system was operating. Upon further inspection tech did find power wires to variable speed blower motor was not tight enough and would loosen up when blower would ramp up causing system to loose low voltage power. Tech ensured connection was secured properly and cycled system. System is operating correctly at this time.


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA INSPECTION on 17 Split Systems and 1 Air Makeup unit. Systems #1, #8, #10, #11 are still down from previous diagnoses on 8/29/23 and 10/4/23. Recommendations and Quotes have been sent previously. System #3 is down due to multiple challenges with blower motor, blower control relay and etc. Due to age and multiple challenges, tech recommends replacement system. System #5 is down due to failed blower motor module. Tech has attached estimate to invoice for replacement. System #2 is operating at this time but blower motor is operating over listed FLA, due to age and cost of repairs tech does recommend replacing system. Tech has attached estimate for repair to invoice for cost comparison. Systems #4 and #16 are in need of blower capacitors, tech has attached estimates to invoice for repairs. Mr. Shawn did ask tech about the air flow in laundry room. Tech advise that was priced and sent from previous service call on 10/4/23. Mr. Shawn also asked for a quote on mini split sy


Open  T.

Open T. Job Checkin

-Performed CMA full service on 6 split systems and 1 mini split system. -Office split system (Payne 0460) outdoor fan motor capacitor & compressor capacitor tested weak. Recommend replacement of dual run capacitor. Provided estimate $322.61. -Third floor split system: Found condensate pump float switch not providing proper voltage to system. Recommend replacement of pump. Bypassed float switch to leave unit operational. Provided estimate for replacement of condensate pump $508.93. -Meeting room split system: Maintenance declines service to system air handler. States equipment is inaccessible due to renovations/storage. -Fitness Center Split System: Evaporator severely rusted. Deterioration of evaporator coil likely to cause condensation drainage issues. Cooling temperature difference not as expected. System ~15+ yr old, R22. Recommend replacement of system. -Kitchen split system: Cleared blockage in primary drain line with vacuum at drain location under 3 compartment sink. Recomme


Luis R.

Luis R. Job Checkin

Tech spoke with Scott he informed tech they wanted to add a extra supply vent to the laundry room since a supply and return are 4 ins apart and just feeding air into itself tech took pictures. Unit 8 s#6793 tech found Daikin feeding the back hallway was low on refrigerant 88/229 410a tech recommended leak search. Unit 10 s#FS4S tech found low on refrigerant 62/167 r22 feeding the hair salon and hallway tech recommends leak search. Unit 11 s#S74F unit is low on refrigerant 57/154 r22 tech recommend leak search tech also found od 1/4 hp fan motor over amping at 1.48a fla is 1.30a tech tested capacitor capacitors tested 24/4.89mfd for a 25/5mfd tech can also hear the bearing on the od motor louder then normal indicating od fan motor is starting to fail tech recommend od fan motor Perform leak search on 3 systems and od fan motor on system 11 s#S74F Jeff Cupp approved leak search’s tech found evaporator coils leaking bottom side of unit 11, back side of coil on unit 10 and mid way of coi


David  S.

David S. Job Checkin

System indoor fan is bad, that is the main reason for coil freezing up. Observed the compressor sounding like it had rocks in it. Quoted $5851.81 to replace compressor, blower motor and relay. Recommend new system due to age and condition. Left system off for now. Model 2twa0048a3000ab Serial number is 4442txg4f d84


Dalton  B.

Dalton B. Job Checkin

Unit #17


Dalton  B.

Dalton B. Job Checkin

Unit #14


Dalton  B.

Dalton B. Job Checkin

Unit #12


Dalton  B.

Dalton B. Job Checkin

Unit #6


Jesse J.

Jesse J. Job Checkin

Tech returned to replace capacitors on AHU# 9, 10, 13, and HP Cond # 15 and 16. Tech also replaced condenser fan motor and capacitor on HP Cond #4. Tech also repaired jumped wire and installed fuse on disconnect for HP Cond #1. All units are up and operating at this time. Tech has attached pictures of repairs to invoice.


Spencer C.

Spencer C. Job Checkin

Tech replaced CMA filters at return tech found no challenges at todays visit.


Jesse J.

Jesse J. Job Checkin

Tech preformed CMA FULL SERVICE on 17 split systems. Systems 6, 12, 14, and 17 are all in need of replacement. System 5 needs electrian to diagnose power issue to air handler, further information is on system performance repot. All other units are operating at this time but need some repairs. Tech has attached system performance reports and estimates for any needed repairs.