Randy K.

Randy K. Job Checkin

Completed filter change on 3 TRANE gas package units, washed 5 make up Air screens, filters in kitchen was just replaced by employees this week.


Derek J.

Derek J. Job Checkin

Tech came to ascertain challenge with kitchen system heating. Tech found igniter wire had become disconnected from the ignition control preventing unit from heating. Tech reconnected igniter wire and tested operation of gas heat. System is working correctly. Tech also configured new thermostat to utilize remote sensor in kitchen area since thermostats are located in the office. The remote sensor is functional however in poor condition, replacement of sensor is recommended. Office will need to quote if interested in replacing.


Joshua  C.

Joshua C. Job Checkin

Tech performed CMA full service on 3 gas package units, 2 make up air units, and 4 exhaust fans. Upon inspection tech found the spark igniter wire on RTU #1 was severed and will not heat. Technician has confirmed repairs are scheduled. Tech has attached system performance reports to this invoice.


Matthew L.

Matthew L. Job Checkin

Replaced smoke detector. Confirmed wiring with Derek. New smoke detector is shutting down unit when tripped, relay on detector and red led are chattering even on new detector while tripped. Led is not solid red on while tripped. Tech suspects older thermostat wire between remote switch and unit. System is cooling and detector is not currently tripped. Per Derek, left unit cooling as is. Install warranty.


Anthony  B.

Anthony B. Job Checkin

ANTHONY AND CHRIS


Matthew L.

Matthew L. Job Checkin

Tech found newly installed RTU3 kitchen unit cooling normally. Tech applied anti corrosion treatment to both micro channel coils and allowed to dry for 30 minutes per instruction on can. Restored power to new kitchen unit. RTU2 had a 24 volt call from thermostat for cooling, but neither blower, fan motors, nor compressors are running due to ESTOP switch open. Bypassed ESTOP for testing. Circuit 2 compressor has been converted from R22 to MO99 R438A and has only 90 psi of standing pressure. No liquid refrigerant. Circuit 2 holds 13 lbs of R22. Confirmed circuit 2 nearly void of MO99. Circuit 1 runs, but tech estimates circuit about 10 lbs low on R22. Holds 25 lbs of R22. Leak searching RTU2 would be $367.49. Repairing system would take 38 lbs of R22. System replacement is recommended. Tech found ESTOP on RTU1 open as well. Tech bypassed for testing and found system cooling normally. R22 pressures are in specs on circuit 1. Circuit 2 has been converted to MO99 and appears to be cool


Anthony  B.

Anthony B. Job Checkin

QUEST 155 DEHUMIDIFIER


Derek J.

Derek J. Job Checkin

Kitchen Unit- Trane 17.5-Ton Gas Pack


Kyle W.

Kyle W. Job Checkin

WE WILL BE REPLACING FAILED DEHUMIDIFIER. FORWARDED INFORMATION TO COLBY.